Technovation Systems, Inc.

Up

Model 2001
In-Duct Bactericidal* 99.9% @ 0.3 Um Filters


Electrically Enhanced Filter (EEF)**

Submittal Drawings
(Printable Version- )

Engineering/Application Data.
 

 

Enables Lower Initial and Operating Cost
Download related technical paper

Low Energy Consumption 
0.4 W/scfm and yet has 
Enough fan power to overcome 
return and supply flow restriction


Recirculating Airflow

Compact Unit with High Flow

Also available w/o fan

Ultra Quiet Operation
 

For Class 1-6: Two terminal ceiling HEPA filters per Model 2001 are recommended, resulting in system filtration efficiency of ~ 99.99999% @ 0.1- 0.3Um
For Class 7 and above: No terminal HEPAs are necessary. Eight 2x2 diffusers per Model 2001 ceiling diffusers are recommended.
.
# of 30”x 24” Filters: 1 Length:18”/ 45.7cm
Height: 26”/ 66cm Weight: 103#/ 46kg
Width: 32”/ 81.3cm Shipping Weight: 128#/ 58kg
Add 6” to width for electrical box.
 
Other Features: Benefits:
  • Bactericidal* -Traps and kills Bacteria* due to ionizing radiation
  • Independent airflow rate/distribution control – higher room coverage
  • Quick filter changes done outside room
  • Distributed air handling connects to conventional lower weight A/C units
  • Low weight –Easily installs in ceiling space 
  • No plenum required –Leaks eliminated
  • Remote ON-OFF control/indicators
  •  Easily ducted for negative pressure
  • Lower bio burden –inhibits growth  through filter and shedding of bacteria
  • Higher performance at lower airflow & lower energy consumption
  • No contamination during filter changes
  • Lower initial cost –roof reinforcements may not be required
  • Lower installation cost  
  • Lower initial cost –Less leakage
  • Ease of control and monitoring
  • Ideal for hospital and other isolators

Click here for information regarding bactericidal effects
.

MODEL   POWER  
AMPERAGE  
AMPS 60Hz.   AMPS 50Hz.  
CBA  
HP  
60H 50Hz
FLOW*** scfm  
60Hz   50Hz  
2001B-1 208-230, 50/60Hz., 3 Phase 2.1A   1.8A   5 1.07   .78   1,550   1,350
2001B-2 440-460VAC, 50/60Hz., 3 Phase   1.3A   1.2A   5 1.07   .78   1,550   1,350
2001B-3 208-230VAC, 50/60Hz., Single Phase   3.5A   2.75A   10 1.07   .78   1,550   1,350

2001B-4

115VAC, 50/60Hz., Single Phase   7A   5.5A   15 1.07   .78   1,550   1,350
2001B-5 380-400VAC, 50Hz., 3 Phase   N/A 1.5A  5 1.07   .78   N/A 1,250

* Based on independent laboratory testing using Escherichia coli and Staphylococcus epidermidis.
** Patented, April 1995, US Patent 5,403,383.
*** Free flow. 

[ Home ][ Contact Us ] [ Publications & Presentations ] [ Filters ]  [ Cleanrooms-BSLabs] [ Hospital/USP 797 ]  [ Flow Bench ] [ Links]
Please Contact Us with questions or comments about this web site.
Copyright © 2002, 2010 Technovation Systems Inc
Last modified: February 05, 2010